Lightning Arrestor
A sacrificial path to earth for the coax, so a surge does not go looking for your radio.
The station earth electrode — the reference everything else bonds to.
| Length | 2.4 m (8 ft) is the common minimum |
|---|---|
| Material | Copper-bonded steel, or solid copper for aggressive soils |
| Diameter | Typically 12-16 mm |
| Target resistance | Under 5 ohm is good; under 25 ohm is the usual safety requirement |
| Depth | Driven below the frost line where possible |
| Bonding | All rods bonded to a common bus with wide, short conductors |
| Inspection | Clamp and conductor checked annually for corrosion |
A ground rod is a copper-bonded steel electrode driven into the soil to give the station a low-impedance connection to earth. It serves two purposes: it provides a fault-current path for electrical safety, and it gives lightning and static discharge somewhere to go other than through your equipment.
The connection to soil is what matters, and soil is a poor conductor. A single rod may measure 25 to 100 ohms depending on moisture and soil type. Multiple rods spaced at least their own length apart, bonded together, reduce that — which is why a good station earth is a system rather than a single stake.
Before driving any rod, confirm there are no buried services — gas, water, electricity or communications — in the area. Contact with a buried power cable while driving a rod can be fatal. Call the local utility marking service first.